1. Ievads
The SINOTIMER STVP series automatic over-voltage un zem-sējtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, zem stage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltage, zem stage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
Detalizēta lietotāja rokasgrāmata PDF formātā ir pieejama lejupielādei: Lietotāja rokasgrāmata (PDF)
2. Galvenās iezīmes
- Liela apjomatage aizsardzība
- Zem tilpumatage aizsardzība
- Pārstrāvas aizsardzība
- Automātiska atkopšana
- Voltage display (separate ABC phase voltage mērījums)
- Ampere display (separate ABC phase ampere measurement)
- Trīsfāzu ampere unbalance protection
- Phase sequence protection (reverse phase protection)
- Zero line break protection
- Fāzes atteices aizsardzība
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Regulējams pārslodzes skaļumstage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Adjustable fault recovery delay time
- Factory data reset function
3. Produkta specifikācijas
| Atribūts | Vērtība |
|---|---|
| Modeļa numurs | STVP936-1-80A |
| Barošanas avots | 3*127V/220VAC 60Hz |
| Rated Voltage | 220V |
| Fāze | Trīs fāzes |
| Maks. Slodzes strāva | 1~80A Adjustable (default: 80A) |
| Liela apjomatage Aizsardzības diapazons | 121V-150V-OFF Adjustable (default: 140V) |
| Liela apjomatage Recovery Range | 120V-149V (default: 135V) |
| Liela apjomatage Action Time | 0.1~10 seconds (default: 0.2s) |
| Zem tilpumatage Aizsardzības diapazons | 118V-80V-OFF Adjustable (default: 90V) |
| Zem tilpumatage Recovery Range | 118V-91V (default: 95V) |
| Zem tilpumatage Action Time | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Fault Recovery Delay Time | 2~600 seconds (default: 60s) |
| Displeja modelis | LCD |
| Izmēri | 71.5 mm (platums) * 95.2 mm (augstums) * 65.7 mm (dziļums) |
| Uzstādīšana | 35 mm DIN sliede |
| Sertifikācija | CE, RoHS |
4. Drošības informācija
- Uzstādīšanu un apkopi drīkst veikt tikai kvalificēti elektriķi.
- Pirms jebkādu uzstādīšanas vai elektroinstalācijas darbu pārliecinieties, vai strāvas padeve ir atvienota.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Pirms strāvas pieslēgšanas pārliecinieties, vai visi vadu savienojumi ir droši un pareizi.
- Do not operate the device in wet or hazardous environments.
5. Uzstādīšana
5.1. Fiziskie izmēri

5.2 Montāža
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Elektroinstalācijas shēma
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Iestatīšana un konfigurēšana
Lai pārietu uz iestatīšanas režīmu, nospiediet un turiet IESTATĪT button for 3 seconds. Then, continuously press IESTATĪT to cycle through the parameters. Use the ▲ un ▼ buttons to adjust the values. When "ENd" appears, press IESTATĪT again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing IESTATĪT, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Solis | Saturs | LCD displejs | Description / Range (Default) |
|---|---|---|---|
| 1 | Liela apjomatage aizsardzības vērtība | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | Liela apjomatage atkopšanas vērtība | Uvor 250V | 220 V–299 V (250 V) |
| 3 | Liela apjomatage aizsardzības darbības laiks | 0.2S | 0.1–10 s (0.2 s) |
| 4 | Zem tilpumatage aizsardzības vērtība | Uve 160V | 219V-150V-OFF (160V) |
| 5 | Zem tilpumatage atkopšanas vērtība | Uver 180V | 151 V–220 V (180 V) |
| 6 | Zem tilpumatage aizsardzības darbības laiks | 0.2S | 0.1–10 s (0.2 s) |
| 7 | Virsstrāvas aizsardzības vērtība | >In 80A | 1-80A (80A) |
| 8 | Over-current protection action time | 5S | 1–512 s (5 s) |
| 9 | 3 fāzes amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 fāzes amp unbalance protection action time | 1.0 S | 0.1–10 s (1 s) |
| 11 | Fāzu secības aizsardzība | ON ABC | ON or OFF (ON) |
| 12 | Ieslēgšanas aizkaves laiks | 2 S | 2–255 s (2 s) |
| 13 | Fault recovery delay time | 60 S | 2–512 s (60 s) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Beigas | BEIGAS | Press SET to save and exit. |
6.2 Rūpnīcas atiestatīšana
To reset the device to factory settings, press and hold the ▲ un ▼ pogas vienlaicīgi 3 sekundes.
7. Darbība
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
Pārsnieguma gadījumātage, zem stage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
8. Traucējummeklēšana
8.1 Kļūmes izmeklēšana
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltage notikumi.
- "<U" for undervoltage notikumi.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Apkope
- Turiet ierīci tīru un bez putekļiem un mitruma.
- Regularly check wiring connections for tightness and signs of wear or damage.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Garantija un atbalsts
For technical support, inquiries, or warranty claims, please contact the distributor:
Izplatītājs: XNY INTERNATIONAL LIMITED
Adrese: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Tālr.: 0086 57761733853
Fakss: 0086 577 89736991
WhatsApp: 0086 1565857 3377
Wechat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
E-pasts: info@sinotimer.com